Thermometer hygrometer with Ethernet interface and relays, cable 4 meters
Ambient humidity, temperature Ethernet sensor on cable with two relay outputs.
Sensor H3531 is designed for online monitoring of temperature, relative humidity of air without aggressive substances. Three binary inputs to detection of two-states signals are the advantage. Other devices are controlled by two relay outputs.
High precision capacitive polymer sensor ensures excellent long term calibration stability and ultimate accuracy. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy.
The device is supplied with T+RH probe with 4 meters cable.
Processing and analysis of measured data:
- online in COMET Cloud
- COMET Database software
- integration into 3-party systems
-
codeH3531-4
-
Warranty3 years
- $878
Technical data
Measured value
Temperature
Relative humidity
Counted values (dew point…)
Two-state signal
TEMPERATURE SENSOR
Measuring range
-30 to +105 °C
Accuracy
±0.4 °C
Resolution
0.1 °C
HUMIDITY SENSOR
Measuring range
0 to 100 % RH
Accuracy
±2.5 % RH from 5 to 95 % at 23 °C
Resolution
0.1% RH
DEW POINT
Measuring range
-60 to +80 °C
Accuracy
±1.5 °C at ambient temperature T <25 °C and RH >30 %
Resolution
0.1 °C
RELAY OUTPUTS
Quantity
2
Maximal voltage
50 V
Maximal current
2 A
Maximal power
60 VA
BINARY INPUTS
Quantity
3
Signal for binary inputy
dry contact, open collector or two-state voltage signal.
Inputs are not galvanically isolated.
Inputs are not galvanically isolated.
Minimum pulse duration on binary input
500 ms
Voltage across open contact
< 3,3 V
Low voltage level
0 to +0,5 V
High voltage level
+3,0 to +30 V
GENERAL TECHNICAL DATA
Operating temperature
-30 to +80 °C
Channels
1x connectable temperature+humidity probe
Acoustic alarm
from built-in beeper - switchable
Counted values
humidex, dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
Output
Ethernet
Measuring interval
2 s
Range of humidity sensor temperature compensation
all temperature range
Available temperature units
degrees Celsius, degrees Fahrenheit
Communication protocol
WWW, ModbusTCP, SNMPv1, SOAP, XML
Alarm protocols
E-mail (SMTP authentication is supported), SNMP Trap, Syslog
Power
9-30 Vdc
Protection class
IP40
Dimensions
136 x 159 x 45 mm; length/diameter of external probe 88/18 mm
External probe cable length
4 meters
Weight
approx. 410 g
Warranty
3 years